CHENZHU safety fence GS8572-EX.RTD
1
  • CHENZHU safety fence GS8572-EX.RTD
2
views: 200

CHENZHU safety fence GS8572-EX.RTD

Rate:
0.0000/5

( 0 reviews )

Item NO.: V029129 MOQ: 0
Weight:    0kgs
Package Size:  
 Price:
$0.00
 Qty:
      $0.00
 Shipping:   Calculate Shipping Cost

DWCT


GS8572-EX.RTD one in and out thermal resistance input isolation barrier
The isolation safety grid converts the thermal resistance signal in the field into the current signal or voltage signal, and transmits it from the danger area to the safe area.It can configure the measurement mark and range range through the computer.The product needs independent power supply, power supply, input and output three isolation.



essential parameter
Number of channels 1 in 1 out
Temperature drift of 0.01%F.S./℃
The response time of 1s reached 90% of the final value
Insulation strength of non-safety end ~ 2500V AC, power supply ~ 500V AC
Insulation resistance is not primary safety end ~ 100M, power supply ~ 100M
Electromagnetic compatibility compliant with IEC 61326-1 (GB / T 18268)
Explosion-proof sign [Ex ia Ga] C; [Ex iaD]
Weight is about 150g
Second line resistance for connected field equipment; third line resistance
The applicable place shall be installed in a safe place and can be connected with the main safety instrument in zone 0, maximum in zone IIC, Zone 20, IIIC dangerous places
data-in
Input signal Pt100 / Cu50 / Cu100 thermal resistance
output data
Output signal is 0~20mA; 4~20mA; 0~5V; 1~5V
Current output load resistance RL 300
Voltage output load resistance RL 35k
The alarm indicator is below the lower range limit, L indicator flashes, the output current is about 3.8mA; above the upper range limit, H indicator flashes, the output current is about 20.8mA; during line breaking, L and H indicator flashes simultaneously, the output current is about 20.8mA; during short circuit, L and H indicator flashes simultaneously, the output current is about 3mA
source
Power supply voltage (Ue) 20~35V DC
Power supply protection Power supply is in reverse protection
Consumption current (24V power supply, 20mA output) 40mA
Power supply mode, independent power supply
Power connection mode guide rail bus power supply; terminal power supply
size
Deep in the 118.9mm
Height of 106.0mm
Width of 12.5mm
hull
Brand Germany Phoenix custom
material PC
Protection level, IP20
Flame retardant grade UL94 / V0
Color ash
product certification
Authenticate the NEPSI; IECEx; SIL
approval standards
NEPSI [Ex ia Ga] IIC meets GB 3836.1, GB 3836.4, GB 3836.20 [Ex iaD] meets GB 12476.1, GB 12476.4
IECEx [Ex ia Ga] IIC meets IEC 60079-0, IEC 60079-11, and IEC 60079-26
Functional security SIL2 is IEC 61508 compliant
Security Data (EX)
Maximum voltage of Um 250V
Maximum output voltage Uo 8.5V (7,8,9,10 terminals)
Maximum output current of Io 20mA (7,8,9,10 between terminals)
Maximum output power Po 43mW (7,8,9,10 terminals)
C Maximum external inductor Lo 3.6mH (between 7,8,9,10 between terminals)
C Maximum external capacitor Co 6.5 F (7,8,9,10 between terminals)
B Maximum external inductor Lo 10.8mH (7,8,9,10 terminals)
B Maximum external capacitor Co 60μF (7,8,9,10 between terminals)
A Maximum external inductor Lo 28.8mH (7,8,9,10 between terminals)
A Maximum external capacitor Co 1000μF (7,8,9,10 between terminals)
Safety-related parameters (SIL)
Device type Type B
Safety and Integrity Level (SIL) 2
Mode of operation (low requirements) IEC 61508-Low requirements
(Low requirement) Safety Failure fraction (SFF) 0.945
(Low requirement) Inspection and test interval (PTI) of 2 years
(Low requirement) λS 499.9 FIT
(Low requirement) λSD 69.54 FIT
(Low requirement) λDU 33.92 FIT
(Low requirement) λDD 13.59 FIT
(Low requirement) Average probability of failure (PFDAVG) 0.000297
(Low requirement) Diagnostic coverage (DC) 0.286
Mode of operation (high requirements) IEC 61508-high requirements
(High requirement) Safety Failure fraction (SFF) 0.945
(High requirement) Inspection and test interval (PTI) of 2 years
(High requirement) λS 499.9 FIT
(High requirement) λSD 69.54 FIT
(High requirement) λDU 33.92 FIT
(High requirement) λDD 13.59 FIT
(High requirement) hourly failure probability (PFH) 3.39E-08
(High requirement) Diagnostic coverage (DC) 0.286
EMC data
The disturbance resistance of electric fast transient pulse group is IEC 61326-3-1; it meets the requirements of FS performance criterion
Surge (impact) resistance: IEC 61326-3-1; FS performance criteria
The radiation resistance of RF electromagnetic field is based on the standard: IEC 61326-3-1; it meets the requirements of FS performance criterion
Electrostatic discharge disturbance resistance to the standard: IEC 61326-3-1; meet the requirements of FS performance criterion
The standard of RF field induction is IEC 61326-3-1; meet FS performance criteria
Low frequency common mode conduction standard: IEC 61326-3-1; meet FS performance criteria
service environment
Continuous operating temperature-20℃ ~ + 60℃
Storage temperature: -40℃ ~ + 80℃
Relative humidity is 10%~90%
The environment requires that there shall not be any strong vibration, impact, large current and sparks and other electromagnetic induction marketing in the surrounding environment, the air should not contain the corrosion of chromium, nickel and silver coating medium, should not contain flammable and explosive substances
Connection parameter
The rigid conductor has an available cross-section range of 0.5~2.5mm²
Flexible conductors may have a cross-section range of 0.5~2.5mm²
Minimum wire cross-section of AWG 12
Maximum wire cross-section of AWG 24
The length of the peeling line is 8mm
Threaded M3
Connecting mode, and screw connection
Minimum tightening torque is 0.5 Nm
Maximum tightening torque is 0.6 Nm
install
Installation mode: DIN35mm guide rail installation

 
No comment
Total 0 records, divided into1 pages. First Prev Next Last
View History
Business time
9:00-22:00
  • Email:support@rig123.com