Schneider Compact NSX160N Micrologic 2.2 160 A - 3P 3D LV430775
1
  • Schneider Compact NSX160N Micrologic 2.2 160 A - 3P 3D LV430775
2
views: 4995

Schneider Compact NSX160N Micrologic 2.2 160 A - 3P 3D LV430775

Rate:
0.0000/5

( 0 reviews )

Item NO.: V020969 MOQ: 0
Weight:    2.2kgs
Package Size:  
 Price:
$126.02
 Qty:
      $126.02
 Shipping:   Calculate Shipping Cost

Schneider Compact NSX160N Micrologic 2.2 160 A - 3P 3D LV430775

in stock

Product range Compact
Product Name Compact NSX
Product Type Circuit Breaker
Product short name Compact NSX160N
Product Application Distribution Protection
Number of poles 3P
Protection pole description 3t
Network Type AC
Network frequency 50/60 Hz
Rated current [In] 160 A on ... 40 °C
Rated insulation voltage [Ui] 800 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp] 8 kV
Rated operating voltage [Ue] 690 V AC 50/60 Hz
Breaking capacity N 50 kA 415 V AC
Breaking capacity 10 kA on ... 600 V AC 50/60 Hz in accordance with UL 508
85 kA on... 240 V AC 50/60 Hz in accordance with UL 508
10 kA Icu on 660/690 V AC 50/60 Hz in accordance with IEC 60947-2
35 kA Icu on 525 V AC 50/60 Hz in accordance with IEC 60947-2
50 kA on... 480 V AC 50/60 Hz in accordance with UL 508
36 kA Icu on 500 V AC 50/60 Hz in accordance with IEC 60947-2
50 kA Icu on... 380/415 V AC 50/60 Hz in accordance with IEC 60947-2
50 kA Icu on 440 V AC 50/60 Hz in accordance with IEC 60947-2
90 kA Icu on... 220/240 V AC 50/60 Hz in accordance with IEC 60947-2
Use breaking capacity [Ics] 10 kA on 660/690 V AC 50/60 Hz in accordance with IEC 60947-2
35 kA on... 525 V AC 50/60 Hz in accordance with IEC 60947-2
36 kA on ... 500 V AC 50/60 Hz in accordance with IEC 60947-2
50 kA on... 380/415 V AC 50/60 Hz in accordance with IEC 60947-2
50 kA on 440 V AC 50/60 Hz in accordance with IEC 60947-2
90 kA on... 220/240 V AC 50/60 Hz in accordance with IEC 60947-2
Isolation function Applicable to EN 60947-2
Applicable to IEC 60947-2
Use category AC class
Trip unit name Micrologic 2.2
Disclaimer: This document does not represent or is used to determine suitability or reliability for a particular user application.
2019-8-9
1
Trip unit type electronic
Trip unit protection LSoI
Pollution degree 3 in accordance with IEC 60664-1
Additional information
Control type handle
Installation type Fixed
Installation method
Connection method - upper end front connection
Connection method - lower end front connection
Auxiliary contact type
Mechanical life 40000 times
Electrical life 10000 times 440 V In/2 in accordance with IEC 60947-2
15,000 times 690 V In/2 in accordance with IEC 60947-2
20000 times 440 V In complies with IEC 60947-2
7500 times 690 V In complies with IEC 60947-2
Phase spacing 35 mm
Local signal indicator LED 90 % Ir
LED 105 % Ir
LED ready
Protection type Overload protection (long delay)
Short time short-circuit protection with fixed delay
Short circuit transient protection
Trip unit rating 160 A on ... 40 °C
Long delay current setting type 9 adjustable
Long delay current setting [Ir] 0.9...1 x Io
Long delay time setting type
[Tr] Long delay time setting range 11 s on... 7.2 x Ir
16 s on... 6 x Ir
400 s on... 1.5 x Ir
Thermal memory 20 minutes before tripping and after tripping
Short delay current setting type 9 adjustable
Short delay current setting [Isd] 1.5...10 x Ir
Short delay time setting type fixed type
Instantaneous protection current setting type
Instantaneous protection setting [Ii] 2400 A
Height 161 mm
Width 105 mm
Depth 86 mm
Product weight 2.2 kg
Model NSX160
surroundings
Overvoltage category Class II
Electric shock protection level Class II
Compliance with standards EN/IEC 60947
UL 508
Product Certification EAC
CCC
Maritime
IP protection class IP40 in accordance with IEC 60529
IK protection level IK07 in accordance with IEC 62262
Operating temperature -35...70 °C
Storage environment temperature -55...85 °C

 
No comment
Total 0 records, divided into1 pages. First Prev Next Last
View History
Business time
9:00-22:00
  • Email:support@rig123.com