ZZ
NJ5-18GK-N-150
delivery time: in stock
Datasheet excerpt: Technical data of NJ5-18GK-N-150
General specifications
Switching function
Normally closed (NC)
Output type
NAMUR
Rated operating distance
5 mm
Installation
flush
Assured operating distance
0 ... 4.05 mm
Reduction factor rAl
0.4
Reduction factor rCu
0.3
Reduction factor r304
0.85
Output type
2-wire
Nominal ratings
Nominal voltage
8.2 V (Ri approx. 1 kΩ)
Switching frequency
0 ... 500 Hz
Current consumption
Measuring plate not detected
min. 3 mA
Measuring plate detected
≤ 1 mA
Functional safety related parameters
MTTFd
4542 a
Mission Time (TM)
20 a
Diagnostic Coverage (DC)
0 %
Compliance with standards and directives
Standard conformity
NAMUR
EN 60947-5-6:2000
IEC 60947-5-6:1999
Standards
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval
Equipment protection level Ga
IECEx PTB 11.0037X
Equipment protection level Gb
IECEx PTB 11.0037X
Equipment protection level Da
IECEx PTB 11.0037X
Equipment protection level Mb
IECEx PTB 11.0037X
ATEX approval
Equipment protection level Ga
PTB 00 ATEX 2048 X
Equipment protection level Gb
PTB 00 ATEX 2048 X
Equipment protection level Da
PTB 00 ATEX 2048 X
EAC conformity
TR CU 012/2011
FM approval
Control drawing
116-0165
UL approval
Ordinary Location
E87056
Hazardous Location
E501628
Control drawing
116-0452
CSA approval
cCSAus Listed, General Purpose
CCC approval
Hazardous Location
2020322315002257
NEPSI approval
NEPSI certificate
GYJ16.1393X
Ambient conditions
Ambient temperature
-40 ... 150 °C (-40 ... 302 °F)
Mechanical specifications
Connection type
cable
Housing material
PPS
Sensing face
PPS
Degree of protection
IP65
Cable
Cable diameter
4.8 mm ± 0.2 mm
Bending radius
> 10 x cable diameter
Material
SIHF
Core cross-section
0.34 mm2
Length
2 m