eneral Information

  • Extended Product Type:
    MS495-63
  • Product ID:
    1SAM550000R1007
  • EAN:
    4013614265457
  • Catalog Description:
    MS495-63 Manual Motor Starter
  • Long Description:
    The MS495-63 manual motor starter is a 70 mm width devices with a rated operational current of Ie = 63.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 25 kA at 400 VAC and the trip class 10. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signalling contacts, undervoltage releases and shunt trips are available as accessory.

Categories

  • Products » Low Voltage Products and Systems » Circuit Breakers » Manual Motor Starters
  • Products » Low Voltage Products and Systems » Control Products » Manual Motor Starters » Manual Motor Starters

Ordering

  • EAN:
    4013614265457
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85362010

Dimensions

  • Product Net Width:
    70 mm
  • Product Net Height:
    165 mm
  • Product Net Depth:
    174 mm
  • Product Net Weight:
    2.247 kg

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    76.5 mm
  • Package Level 1 Height:
    171 mm
  • Package Level 1 Length:
    190 mm
  • Package Level 1 Gross Weight:
    2.262 kg

Environmental

  • Ambient Air Temperature:
    Operation -20 ... +70 °C
    Operation Compensated -20 ... +60 °C
    Storage -50 ... +80 °C
  • Ambient Air Temperature Compensation:
    Yes
  • Maximum Operating Altitude Permissible:
    2000 m
  • Resistance to Shock acc. to IEC 60068-2-27:
    11 ms Pulse 25g
  • RoHS Status:
    Following EU Directive 2002/95/EC August 18, 2005 and amendment

Technical UL/CSA

  • Maximum Operating Voltage UL/CSA:
    Main Circuit 600 V AC
  • Ampere Rating UL/CSA:
    63 A
  • Horsepower Rating UL/CSA:
    (200 V AC) Three Phase 20 Hp
    (208 V AC) Three Phase 20 Hp
    (220 ... 240 V AC) Three Phase 25 Hp
    (440 ... 480 V AC) Three Phase 50 Hp
    (550 ... 600 V AC) Three Phase 60 Hp
  • General Use Rating UL/CSA:
    (600 V AC) 63 A
  • Connecting Capacity Main Circuit UL/CSA:
    Flexible 1x 10 ... 2/0 AWG
    Flexible 1/2x 10 ... 1/0 AWG
    Stranded 1x 10 ... 2/0 AWG
    Stranded 1/2x 10 ... 1/0 AWG
  • Tightening Torque UL/CSA:
    Main Circuit 35 ... 53 in·lb

Additional Information

  • Actuator Type:
    Rotary Handle
  • Connecting Capacity-Main Circuit:
    Flexible with Ferrule 1x 2.5 ... 50 mm²
    Flexible with Ferrule 2x 2.5 ... 35 mm²
    Solid 1/2x 2.5 ... 16 mm²
    Stranded 1x 10 ... 70 mm²
    Stranded 2x 10 ... 50 mm²
  • Conventional Free-air Thermal Current (Ith):
    Main Circuit 63 A
  • Degree of Protection:
    Housing IP20
    Main Circuit Terminals IP00
  • Electrical Durability:
    25000 cycle
  • IIT Publishing Status:
    Level 0 - Information enabled
  • Mechanical Durability:
    50000 cycle
  • Mounting on DIN Rail:
    TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
    TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
  • Mounting Position:
    Position 1 to 6
  • Number of Poles:
    3
  • Number of Protected Poles:
    3
  • Pollution Degree:
    3
  • Power Loss:
    at Rated Operating Conditions per Pole 2.9 … 5.6 W
  • Product Main Type:
    MS495
  • Product Name:
    Manual Motor Starter
  • Rated Current (In):
    63 A
  • Rated Frequency (f):
    Main Circuit 50 Hz
    Main Circuit 60 Hz
  • Rated Impulse Withstand Voltage (Uimp):
    Main Circuit 6 kV
  • Rated Instantaneous Short-Circuit Current Setting (Ii):
    819 A
  • Rated Insulation Voltage (Ui):
    690 V
  • Rated Operational Current (Ie):
    63 A
  • Rated Operational Current AC-3 (Ie):
    63 A
  • Rated Operational Power AC-3 (Pe):
    (400 V) Three Phase 30 kW
  • Rated Operational Voltage:
    Main Circuit 690 V AC
    Main Circuit 450 V DC
  • Rated Service Short-Circuit Breaking Capacity (Ics):
    (230 V AC) 100 kA
    (400 V AC) 25 kA
    (440 V AC) 20 kA
    (500 V AC) 6 kA
    (690 V AC) 3 kA
  • Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics):
    50 %
  • Rated Ultimate Short-Circuit Breaking Capacity (Icu):
    (230 V AC) 100 kA
    (400 V AC) 50 kA
    (440 V AC) 50 kA
    (500 V AC) 12 kA
    (690 V AC) 6 kA
  • Rated Uninterrupted Current (Iu):
    63 A
  • Recommended Screw Driver:
    Hexagon 4
  • RoHS Date:
    0016
  • Setting Range:
    45 ... 63 A
  • Standards:
    IEC/EN 60947-1
    IEC/EN 60947-2
    IEC/EN 60947-4-1
    UL 508
    CSA 22.2 No. 14
  • Tightening Torque:
    Main Circuit 4 ... 6 N·m
  • Wire Stripping Length:
    Main Circuit 17 mm




Contact Information:

 

Wechat: +86 133 5926 9377

Email:  rig123@rig123.com

Skype:  liuyongjie67

QQ: 526354062

 

If you have any questions,pls do not hesitate to contact us .

 

Attention: Please kindly leave us your phone number ,and also a full and accurate shipping address. 

 

Remark : please kindly add our email to your "white-list" or sign"important" then you can get our message successfully every time,like special offer, promotion sale ,technic info , and so on ,thanks !


 
No comment
Total 0 records, divided into1 pages. First Prev Next Last
View History
Business time
9:00-22:00
  • Email:support@rig123.com