PN3094 PN-010-RER14-MFRKG/US/V IFM Pressure Sensor
In stcok
PN3094 PN-010-RER14-MFRKG/US/V IFM Pressure Sensor
Product characteristics
Output signal
switching signal; analogue signal; IO-Link; (configurable)
Measuring range
-1...10 bar
-14.5...145 psi
-0.1...1 MPa
Process connection
threaded connection G 1/4 internal thread M6 I
Application
Special feature
Gold-plated contacts
Measuring element
ceramic-capacitive pressure measuring cell
Media
liquids and gases
Medium temperature [°C]
-25...80
Pressure rating
75 bar
1087 psi
7.5 MPa
Min. bursting pressure
150 bar
2175 psi
15 MPa
Vacuum resistance [mbar]
-1000
Type of pressure
relative pressure; vacuum
Electrical data
Operating voltage [V]
18...30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]
< 35
Min. insulation resistance [MΩ]
100; (500 V DC)
Protection class
III
Reverse polarity protection
yes
Power-on delay time [s]
< 0.3
Integrated watchdog
yes
Inputs / outputs
Number of inputs and outputs
Number of digital outputs: 1; Number of analogue outputs: 1
Outputs
Total number of outputs
2
Output signal
switching signal; analogue signal; IO-Link; (configurable)
Electrical design
PNP
Number of digital outputs
1
Output function
normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]
2.5
Permanent current rating of switching output DC [mA]
150; (200 (...60 °C) 250 (...40 °C))
Switching frequency DC [Hz]
< 170
Number of analogue outputs
1
Analogue current output [mA]
4...20; (0 bar = 4 mA; 10 bar = 20 mA)
Max. load [Ω]
500
Analogue voltage output [V]
0...10; (0 bar = 0 V; 10 bar = 10 V)
Min. load resistance [Ω]
2000
Short-circuit protection
yes
Type of short-circuit protection
pulsed
Overload protection
yes
Measuring/setting range
Measuring range
-1...10 bar
-14.5...145 psi
-0.1...1 MPa
Factory setting / CMPT = 2
Set point SP
-0.9...10 bar
-13.5...145 psi
-0.09...1 MPa
Reset point rP
-0.95...9.95 bar
-14...144.5 psi
-0.095...0.995 MPa
Min. difference between SP and rP
0.5 bar
1 psi
0.005 MPa
In steps of
0.05 bar
0.5 psi
0.005 MPa
Status_B High Resolution / CMPT = 3
Set point SP
-0.92...10 bar
-13.3...145 psi
-0.092...1 MPa
Reset point rP
-0.97...9.95 bar
-14...144.3 psi
-0.097...0.995 MPa
Min. difference between SP and rP
0.5 bar
0.8 psi
0.005 MPa
In steps of
0.01 bar
0.1 psi
0.001 MPa
Accuracy / deviations
Switch point accuracy [% of the span]
< ± 0,5
Repeatability [% of the span]
< ± 0,1; (with temperature fluctuations < 10 K)
Characteristics deviation [% of the span]
< ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation [% of the span]
< ± 0,25
Long-term stability [% of the span]
< ± 0,05; (per 6 months)
Temperature coefficient zero point [% of the span / 10 K]
< ± 0,2; (-25...80 °C)
Temperature coefficient span [% of the span / 10 K]
< ± 0,2; (-25...80 °C)
Response times
Response time [ms]
< 3
Delay time programmable dS, dr [s]
0...50
Damping for the switching output dAP [s]
0...4
Damping for the analogue output dAA [s]
0...4
Max. response time analogue output [ms]
3
Software / programming
Parameter setting options
hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output
Interfaces
Communication interface
IO-Link
Transmission type
COM2
IO-Link revision
1.1
SDCI standard
IEC 61131-9
SIO mode
yes
Required master port type
A
Process data analogue
1
Process data binary
1
Supported DeviceIDs
Type of operation
DeviceID
Factory setting / CMPT = 2
431 d / 00 01 af h
Status_B High Resolution / CMPT = 3
615 d / 00 02 67 h
Note
For further information please see the IODD PDF file at "Downloads"
Factory setting / CMPT = 2
Profiles
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
Min. process cycle time [ms]
2.3
IO-Link resolution pressure [bar]
0.01
IO-Link functions (cyclical)
function
bit length
pressure
14
binary switching information
1
IO-Link functions (acyclical)
application specific tag
Status_B High Resolution / CMPT = 3
Profiles
Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000)
Min. process cycle time [ms]
3
IO-Link resolution pressure [bar]
0.005
IO-Link functions (cyclical)
function
bit length
pressure
16
device status
4
binary switching information
1
IO-Link functions (acyclical)
application specific tag
Operating conditions
Ambient temperature [°C]
-25...80
Storage temperature [°C]
-40...100
Protection
IP 65; IP 67
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-27
50 g (11 ms)
Vibration resistance
DIN EN 60068-2-6
20 g (10...2000 Hz)
MTTF [years]
226
UL approval
UL Approval no.
J004
Pressure Equipment Directive
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight [g]
235.5
Materials
stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC
Materials (wetted parts)
stainless steel (1.4404 / 316L); Al2O3 (ceramics); FKM
Min. pressure cycles
100 million
Tightening torque [Nm]
25...35; (recommended tightening torque; depends on lubrication, seal and pressure rating)
Process connection
threaded connection G 1/4 internal thread M6 I
Restrictor element integrated
no (can be retrofitted)
Displays / operating elements
Display
Display unit
3 x LED, green (bar, psi, MPa)
switching status
1 x LED, yellow
measured values
alphanumeric display, red/green 4-digit
Remarks
Pack quantity
1 pcs.
Electrical connection
Connection
Connector: 1 x M12; Contacts: gold-plated
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — PN3094-02 — 20.08.2019 —