A63-30-11
1
  • A63-30-11
2
views: 571

A63-30-11

Rate:
0.0000/5

( 0 reviews )

Item NO.: abb0067 MOQ: 0
Weight:    2kgs
Package Size:  
 Price:
$66.00
 Qty:
      $66.00
 Shipping:   Calculate Shipping Cost


General Information

  • Extended Product Type:
    A63-30-11 125-127V 50Hz / 150V 60Hz
  • Product ID:
    1SBL371001R3011
  • EAN:
    3471522088307
  • Catalog Description:
    A63-30-11 125-127V 50Hz / 150V 60Hz Contactor
  • Long Description:
    A63 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC / 1000 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The A... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles and 2 built-in auxiliary contacts, front and side-mounted add-on auxiliary contact blocks - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.

Ordering

  • EAN:
    3471522088307
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85369085

Dimensions

  • Product Net Width:
    82 mm
  • Product Net Depth:
    108 mm
  • Product Net Height:
    110 mm
  • Product Net Weight:
    1.200 kg

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    140 mm
  • Package Level 1 Length:
    146 mm
  • Package Level 1 Height:
    96 mm
  • Package Level 1 Gross Weight:
    1.2 kg
  • Package Level 1 EAN:
    3471522088307
  • Package Level 2 Units:
    63 piece
  • Package Level 3 Units:
    160 piece

Technical

  • Number of Main Contacts NO:
    3
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    1
  • Number of Auxiliary Contacts NC:
    1
  • Standards:
    Devices complying with international standards IEC 947-1 / 947-4-1, and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to IEC 947-1; EN 60 947-1 and amendment 2 to IEC 947-4-1
  • Rated Operational Voltage:
    Main Circuit 1000 V
  • Rated Frequency (f):
    Supply Circuit 50 Hz
    Supply Circuit 60 Hz
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-4-1, Open Contactors q = 40 °C 125 A
    acc. to IEC 60947-5-1, q = 40 °C 16 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 40 °C 115 A
    (690 V) 55 °C 95 A
    (690 V) 70 °C 80 A
  • Rated Operational Current AC-3 (Ie):
    (1000 V) 55 °C 25 A
    (220 / 230 / 240 V) 55 °C 65 A
    (380 / 400 V) 55 °C 65 A
    (415 V) 55 °C 65 A
    (440 V) 55 °C 65 A
    (500 V) 55 °C 55 A
    (690 V) 55 °C 43 A
  • Rated Operational Power AC-3 (Pe):
    (220 / 230 / 240 V) 18.5 kW
    (380 / 400 V) 30 kW
    (415 V) 37 kW
    (440 V) 37 kW
    (500 V) 37 kW
    (690 V) 37 kW
  • Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
    8 x Ie AC-3
  • Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
    10 x Ie AC-3
  • Rated Operational Current AC-15 (Ie):
    (220 / 240 V) 4 A
    (24 / 127 V) 6 A
    (380 / 440 V) 3 A
    (500 V) 2 A
    (690 V) 2 A
  • Short-Circuit Protective Devices:
    Auxiliary Circuit - gG Type Fuses 10 A
    gG Type Fuses 125 A
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 650 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 135 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 370 A
    for 0.1 s 140 A
    for 1 s 100 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
  • Maximum Electrical Switching Frequency:
    AC-1 600 cycles per hour
    AC-2 / AC-4 150 cycles per hour
    AC-3 600 cycles per hour
  • Rated Operational Current DC-13 (Ie):
    (125 V) 0.55 / 69 A
    (24 V) 6 / 144 A
    (250 V) 0.3 / 75 A
    (48 V) 2.8 / 134 A
    (72 V) 1 / 72 A
  • Rated Insulation Voltage (Ui):
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
    acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
    acc. to UL/CSA 600 V
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Mechanical Durability:
    10 million
  • Maximum Mechanical Switching Frequency:
    3600 cycles per hour
  • Coil Operating Limits:
    (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) °C
  • Rated Control Circuit Voltage (Uc):
    50 Hz 125 … 127 V
    60 Hz 150 V
  • Coil Consumption:
    Average Holding Value 50 Hz 18 V·A
    Average Holding Value 50 Hz 5.5 W
    Average Holding Value 60 Hz 18 V·A
    Average Holding Value 60 Hz 5.5 W
    Average Pull-in Value 50 Hz 180 V·A
    Average Pull-in Value 60 Hz 210 V·A
  • Operate Time:
    Between Coil Energization and NO Contact Closing 8 ... 27 ms
    Between Coil De-energization and NO Contact Opening 4 ... 11 ms
    Between Coil De-energization and NC Contact Closing 7 ... 14 ms
    Between Coil Energization and NC Contact Opening 7 ... 22 ms
  • Connecting Capacity-Main Circuit:
    Flexible with Cable End 6 ... 16 mm²
    Rigid Cable 6 ... 25 mm²
  • Connecting Capacity-Auxiliary Circuit:
    Flexible with Cable End 0.75 ... 2.5 mm²
    Rigid Cable 1 ... 4 mm²
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
  • Connecting terminals (delivered in open position) Main poles:
    M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector
  • Terminal Type:
    Screw Terminals

Environmental

  • Ambient Air Temperature:
    Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C
    Close to Contactor for Storage -60 ... +80 °C
    Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +55 °C
    Close to Contactor without Thermal O/L Relay (Uc) -40 ... +70 °C
  • Climatic Withstand:
    acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
  • Maximum Operating Altitude Permissible:
    3000 m





Contact Information:

 

Wechat: +86 133 5926 9377

Email:  rig123@rig123.com

Skype:  liuyongjie67

QQ: 526354062

 

If you have any questions,pls do not hesitate to contact us .

 

Attention: Please kindly leave us your phone number ,and also a full and accurate shipping address. 

 

Remark : please kindly add our email to your "white-list" or sign"important" then you can get our message successfully every time,like special offer, promotion sale ,technic info , and so on ,thanks !

 



 
No comment
Total 0 records, divided into1 pages. First Prev Next Last
View History
Business time
9:00-22:00
  • Email:support@rig123.com