9907-018 2301A GEN Speed controller
need confirm delivery time
2301A
Load Sharing and Speed Controlmanual operation. An optional deceleration ramp is available.
General Specifications
Power Supply Rating 90–150 Vdc or 85–132 Vac for High Voltage models
20–40 Vdc for Low Voltage models
Power Consumption less than or equal to 15 W nominal
Inputs—
3-phase PT Inputs 90–240 Vac line-to-line, 45–66 Hz. PT input, burden is between 1.5 VA and 1.7 VA per
phase at 240 Vac, and between 0.4 VA and 0.5 VA per phase at 120 Vac
3-phase CT Inputs 3–7 Arms at full load, CT input burden at full load is 0.1 VA per phase
Speed Sensor Input Impedance 100–300 Ω
Speed Sensor magnetic pickup 1.0 Vac minimum to 30 Vac maximum
Speed Trim 0–100 Ω for 0 to 10% speed change
Speed Setting terminals 23–24 jumpered, internally adjustable 100 Ω potentiometer allows external 0–
10% speed trim
Idle Speed Select external switch, open terminals 19 to 16
Droop external switch, open terminals 14 to 16
Synchronizer ±5 Vdc for speed change with Woodward SPM-A synchronizer
Load Sharing 0–6 Vdc
Outputs—
Actuator 7.5 Vdc max for 0 to 214 mA with 35 Ω coil
Adjustments—
Rated Speed 11 450 Hz
Acceleration Ramp (±Idle to Rated) 0–10 s, switch activated, close terminals 19 to 16
Actuator Compensation time constant compatibility 0–500 ms
Low Idle Speed 55% rated
Amplifier Gain
Reset (Stability)
Load Gain 6 Vdc maximum at 5 A CT current
Droop 0 to 10%
Speed Control Range switch selectable, 500–1500 Hz, 1000–3000 Hz, 2000–6000 Hz (standard), 4000–12
000 Hz
Operating Temperature –40 to +85 °C (–40 to +185 °F)
Load Sharing ±5% of rated load with speed setting matched
Vibration 4 Gs, 5 to 500 Hz
Shock 60 Gs
Weight approximately 1.8 kg (4 lb)
Finish gloss powder
Regulatory Compliance
European Compliance for CE Mark (specified low voltage models only)—
EMC Directive Certified to 89/336/EEC COUNCIL DIRECTIVE of 03 May 1989 on the approximation of
the laws of the member states relating to electromagnetic compatibility.
Low Voltage Directive Certified to the 73/23/EEC COUNCIL DIRECTIVE of 19 February 1973 on the
harmonization of the laws of the Member States relating to electrical equipment
designed for use within certain voltage limits.
North American Compliance:
CSA: CSA Certified for Ordinary Locations for use in the United States and Canada.
2301A LSSC Outline Drawing
(Do not use for construction)
METRIC
CONVERSION CHART
MM INCH
4.8 0.188
5.6 0.219
7.1 0.279
19.0 0.748
61.9 2.437
168.3 6.625
174.6 6.874
182.6 7.188
349.2 13.748
387.4 15.251
Contact Information:
Wechat: +86 133 5926 9377
Email: rig123@rig123.com
Skype: liuyongjie67
QQ: 526354062
If you have any questions,pls do not hesitate to contact
us .
Attention: Please kindly leave us your phone number
,and also a full and accurate shipping address.
Remark : please kindly add our email to your "white-list" or sign"important" then you can get our message
successfully every time,like special offer, promotion sale ,technic info , and
so on ,thanks !